19Operating and installation manual for VR 61 mixer module
7.3 Function floor drying
The floor-drying function is used to “heat dry” a freshly-
laid heating layer according to instructions.
h
Note!
The floor drying function is only available for
the controlled heating circuit (HC2)
If this function is activated, all selected operating modes
are stopped.
The flow temperature of the controlled heating circuit is
controlled according to a pre-set program regardless of
the outside temperature.
Starting temperature: 25 °C
Days after starting the
function
Target feed temperature for this day
[°C]
125
230
335
440
545
6-12 45
13 40
14 35
15 30
16 25
17-23
10
(frost protection function,
pump in operation)
24 30
25 35
26 40
27 45
28 35
29 25
Table 7.3 Temperature profile floor drying
The controller VRC 430 or VRC 430f shows, in the
operating level for the expert technician, display screen
C23, the operating mode for floor drying with the
current day and the associated target feed temperature.
The current day can be set manually.
When the function is started, the current time of the
start is saved. The day is
changed exactly at this time.
8 VRC 430 / VRC 430f
Operating level for the operator
The operating level for the operator serves to indicate
and to adjust/modify the basic parameters. The setting/
changing of the parameters can be carried out by the
operator without any special previous knowledge and
during normal operation.
The parameters are shown in various display screens in
the display area of the controller VRC 430 or VRC 430f .
The operating concept is described in the operating and
installation instructions of the controller VRC 430 or
VRC 430f.
The following differences in the displat screens are
produced by the installation of the mixer module VR 61
in the heating system with respect to the standard
configuration as described in the manual for the VRC
430 or VRC 430f:
Display screen G1 simplified basic display
Th. 12.01.06
11:46
3.0 °C Outside
Auto
19.0 °C
VRC 430
Fig. 8.1 Simplified basic display
Depending upon the adjustment method undertaken by
the expert technician, this screen is either not displayed
at all or shows the values from heating circuit 1 or 2.
Ask your expert technician for the current setting.
Display screen G2 basic display
56.0 °C
Auto
> Select room temperature
21.0 °C
Th. 12.01.06
11:46
3.0 °C Outside
HC1
Auto DHW
HC2
20.0 °C Auto
Fig. 8.2 Basic display
Both heating circuits (HC1 and HC2) are displayed in the
basic display. For both heating circuits you can modify
the target room temperature and the operating mode in
each case.
Start-up 7