Vaillant Air/Flue Gas System Installation Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
System conditions 5
0020058722_04 Air/flue gas system Installation manual 13
5.1.2 Flue gas pipe in the shaft, combustion air from the installation room
ecoCRAFT VKK../3-E-HL
806 1206 1606 2006 2406 2806
System
Shaft cross-sec-
tion:
At least
Maximum total pipe length (L1 + L2 + L3)
130 mm
diameter
Round: DN + 60 mm
Angular: DN + 40
mm
33.0 m
plus 3 x 87° diversions and support elbow
160 mm
diameter
50.0 m
plus 3 x 87° diversions and support elbow
200 mm
diameter
50.0 m
plus 3 x 87° diversions and support elbows
The horizontal flue gas pipe must have a maximum length of 6 m, minus the three 87° diversions.
5.1.3 Flue gas pipe in the shaft, combustion air through the external wall
L
2
L
1
L
3
L
4
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 35 36