41Installation and maintenance instructions ecoTEC exclusive 0020017768_05
Troubleshooting 9
9 Troubleshooting
h
Note!
If you wish to contact the Vaillant Service Team,
please refer to the error code displayed (F.xx)
and the appliance status (S.xx) if possible.
9.1 Diagnostics
9.1.1 Status codes
The status codes that you can see on the display
provides information about the current operating
condition of the appliance.
Fig. 9.1 Display of status codes
The display of the status codes can be viewed as follows:
Press the "i" button.
The display shows the status code, e.g. S.4 for
"Burner mode - Heating".
The display of the status codes can be ended as follows:
• Press the "i" button or
Do not press any button for about 4 minutes.
The current filling pressure in the heating system
appears in the display again.
Display Meaning
Heating mode
S.0 No heat required
S.1 Fan start
S.2 Water pump flow
S.3 Ignition
S.4 Burner mode
S.5 Fan and water pump return water
S.6 Fan return flow
S.7 Water pump return water
S.8 Burner lock after heating mode
Hot water function
S.10 Hot water switch on
S.11 Fan start
S.13 Ignition
S.14 Burner mode
S.15 Fan and water pump return water
S.16 Fan return flow
S.17 Water pump return water
Storage tank charging/heat retention mode
Page 20 Water pump flow
S.21 Fan start
S.23 Ignition
S.24 Burner mode
S.25 Fan and water pump return water
S.26 Fan return flow
S.27 Water pump return water
S.28
Burner lock after recharging/heat retention
(cycle suppression)
Other:
S.30
Room thermostat blocks heating operation
(terminal 3’-4’ open)
S.31
Summer mode active or eBUS controller or timer
blocks heating operation
S.32
Heat exchanger antifreeze active, as fan speed
variation is too high. Appliance is within the waiting
time of the operation block function
S.34 Antifrost mode active
S.36
Target value specification of room thermostat
< 20 °C , i.e. the external regulator is blocking
the heating operation
S.41 Water pressure >2.9bar
S.42
Exhaust gas diverter return signal blocks burner
operation (only in connection with accessories) or
condensate pump faulty, heat demand is blocked
S.53
Appliance is within the waiting period of the
modulation block/operation block function due to
water shortage (flow-return spread too large)
S.54
Appliance is within the waiting period of the
operation block function due to water shortage
(temperature gradient)
S.96
Return sensor test running, heating demands
are blocked
S.97
Water pressure sensor test running, heating
demands are blocked
S.98
Flow/return sensor test running, heating
demands are blocked
Table 9.1 Status codes