Installation and maintenance instructions ecoTEC plus 937 0020031552_06 51
8.1.4 Adjusting the CO
2
concentration (or the air
ratio)
a
Danger!
Increased risk of poisoning due to incorrect
settings!
Incorrect setting may increase the risk of poi-
soning.
If one of the flue gas values is greater than
the acceptable values in Table 8.1 then
check
- the integrity of the complete flue gas
installation
- the integrity of the combustion circuit
seals
- the gas inlet working pressure
- the gas flow rate.
If the flue gas value needs to be adjusted,
unfasten the screw (Fig. 8.1, 2) and
fold the air intake pipe (Fig. 8.1, 3) forwards through
90°. Do not remove the air intake pipe.
Specify the required flue gas value if necessary
(value with front casing of boiler removed, see
Table 8.1) by turning the screw of the main throttle
(Fig. 8.1, 1)
i
Use a 4 mm hexagon socket spanner to turn
the screw.
Turn to the left: higher CO
2
concentration,
Turn to the right: lower CO
2
concentration.
i
Natural gas: Only perform the adjustment in
increments of 1/8 turn and wait approxi-
mately 1 minute after each adjustment until
the value stabilises.
Liquid gas: Only perform the adjustment in
very small increments (approximately 1/16
turns), and wait approximately 1 minute after
each adjustment until the value stabilises.
After performing the adjustments, fold the air intake
pipe back up.
Check the CO
2
concentration once again.
If necessary, repeat the setting process.
Push the „i“ button to deactivate the full load mode.
The full load mode is also deactivated if no button is
pushed for 15 minutes.
The adjusting screw shall be sealed after the adjust-
ment.
Re-secure the air intake pipe with the screw (2).
Put the front casing back on.
>
>
>
>
>
>
>
>
>
>
>
>
>
Settings Natural gas (H)
Tolerance
Propane
Tolerance
Unit
CO
2
after 5 minutes full
load mode with
boiler front casing closed
9.2 1,0 10.2 0,5 Vol.–%
CO
2
after 5 minutes full
load mode with boiler
front casing removed
9.0 1,0 10.0 0,5 Vol.–%
Set for Wobbe-Index W
0
15 22.5 kWh/m
3
CO value with full load < 250 < 250 ppm
CO/CO
2
< 0,0031 < 0,0026
Table 8.1 Factory gas settings
a
Danger!
Risk to life due to poisoning!
CO is an extremely toxic gas. Risk to life due
to excessive CO concentrations.
f you are not able to adjust the boiler cor-
rectly and the flue gas values remain
higher than allowed in Table 8.1, call the
Vaillant Service Solutions.
Do not start up the boiler!
>
>
Inspection and maintenance 8