5 Flat roof fitting and installation
48 Installation manual auroTHERM exclusive 0020077994_02
Conditions: Type of installation: Direct mounting
Screwing on the rack
Caution.
Lack of tightness due to destruction of
the roof skin.
In the event of destruction of the roof skin,
water can penetrate the building.
Check the tightness of the roof skin
after tightening screw connections.
Restore the tightness of the roof skin if
necessary.
Define the required rack clearances as described in the
chapter "Defining rack clearances".
Drill the required holes at the defined positions.
Secure the rack with fastenings appropriate to the base
(diameter: at least 10 mm).
Mount as many racks as you need to hold the collectors.
Conditions: Type of installation: Floating installation (with load plates)
Preparing load plates
Caution.
Lack of tightness due to destruction of
the roof skin.
In the event of destruction of the roof skin,
water may penetrate the building.
Ensure adequate protection of the roof
skin during installation on roof sealing
surfaces.
Place large-area, non-slip building pro-
tection mats underneath the installation
system.
If the roof is covered with gravel, remove the gravel at
the places where you wish to position the load plates,
and use non-slip building protection mats to protect the
roof skin.
Connect two load plates as shown in the illustration.
Connect two additional load plates as shown in the illus-
tration.
Note
For each rack, you will need four load plates:
one pair each for the front and rear rack
feet.