Commissioning
Installation and maintenance instructions ecoTEC plus 0020116700_06 39
10
10 Commissioning
At the time of commissioning, complete all relevant sec-
tions of the benchmark checklist found within the back
pages of this document.
Ensure that the filling and purging programs P.06 and P.00
have been allowed to run fully before the boiler is ignited
for the first time.
a
Danger!
Risk of poisoning and burns caused by
escaping hot flue gas!
Hot flue gas can escape and cause poison-
ing and burns if the boiler is operated with
an incompletely mounted or open air/flue
gas duct or if the boiler is operated with
internal leaks with the front casing open.
> Operate the boiler
- for commissioning
- for testing purposes
- in continuous operation
only when the front casing is fitted and
closed and the air/flue gas duct is com-
pletely mounted.
> Exclusively for test purposes such as gas
working pressure testing the boiler may
be operated with the front casing
removed for short durations ONLY but
must have a completely mounted air/flue
gas duct.
i
The automatic air vent cap must be loosened
before filling the heating circuit or recharging
circuit and during operation.
Purge the heating circuit and the recharging cir-
cuit using the purging program P.00
(¬section10.4).
Auxiliary service equipment:
The following test and measuring equipment is required for
commissioning:
–CO
2
measuring instrument
Digital or U-tube manometer
10.1 Switching on the boiler
> Press the on/off button (¬Operating instructions).
The basic display appears on the display.
10.2 Installation assistant
The installation assistant is launched when switching on the
boiler for the first time. It provides easy access to the most
important test programs and configuration settings for
installing the boiler. The installation assistant is displayed
whenever the boiler is switched on until it has been suc-
cessfully completed.
You must confirm the start of the installation assistant.
Once confirmed, all of the heating and hot water demands
from the boiler are blocked. This status remains until the
installation assistant is completed or cancelled.
If you do not confirm the start of the installation assistant,
it will be closed 10 seconds after being switched on and the
basic display will appear. The next time the boiler is
switched on using the on/off button, the installation assist-
ant will be started again.
10.2.1 Language
> Select the required language using the minus or plus
button.
> Press the right selection button to confirm the selected
language.
The language change must be confirmed a second time in
order to avoid an unintentional change.
i
If you unintentionally select a language that you
cannot understand, you can change it again as
described below.
> Press the right selection button and the plus button
simultaneously and hold them down.
> Press the fault clearance key for a short time.
> Keep the right selection button and the plus button
pressed until the option for changing the language
appears on the display.
> Select the language of your choice using the minus key
or the plus key.
> Confirm the change by pressing the right-hand selection
button ("OK").
10.2.2 Filling mode
Filling mode (test program P.06) is activated automatically
in the installation assistant for as long as it appears on the
display. (¬section 10.4).
10.2.3 Purging
> Start test program P.00 to purge the system
(¬section10.4).
Unlike the way in which it is started in the test programs
menu, the purge program P.00 is started in the installa-
tion assistant by pressing the minus button or the plus
button.
In order to change the circuit that is being purged, you
can press the right selection button.