For the installer
ecoTEC plus 612
ecoTEC plus 615
ecoTEC plus 618
ecoTEC plus 624
ecoTEC plus 630
ecoTEC plus 637
ecoTEC plus 824
ecoTEC plus 831
ecoTEC plus 837
ecoTEC pro 28
ecoTEC pro 24
Instructions for installation and servicing
ecoTEC
Wall hung room sealed fan assisted condensing boiler
GB, IE
Page view 0
1 2 3 4 5 6 ... 63 64

Summary of Contents

Page 1

For the installerecoTEC plus 612ecoTEC plus 615ecoTEC plus 618ecoTEC plus 624ecoTEC plus 630ecoTEC plus 637ecoTEC plus 824ecoTEC plus 831ecoTEC plus 8

Page 2 - Contents

10 Instructions for installation and servicing ecoTEC 839592_123 General requirements3.1 Preliminary remarks for room sealed appliancesThis appliance

Page 3

11Instructions for installation and servicing ecoTEC 839592_12 12347865Fig. 3.1 Contents included with delivery of ecoTEC plus system boilersDO NOT r

Page 4 - 1 Introduction

12 Instructions for installation and servicing ecoTEC 839592_12bari F P1237654Fig. 3.3 Contents included with delivery of ecoTEC pro combi-nation bo

Page 5 - Introduction 1

13Instructions for installation and servicing ecoTEC 839592_12 their contractor. An existing meter should be checked to ensure that it is capable of p

Page 6 - 2 Boiler specifications

14 Instructions for installation and servicing ecoTEC 839592_12ABCDAGH, IFJBFMLLKKGGFFEAAFig. 3.8 Flue termination NoteVertical flues must not termina

Page 7 - Boiler specifications 2

15Instructions for installation and servicing ecoTEC 839592_12 3.10 Guide to system requirements3.10.1 Water circulation systemDetailed recommenda

Page 8

16 Instructions for installation and servicing ecoTEC 839592_12Total heating outputTotal hardness at 20 l/kW for the smallest boiler heating surface2)

Page 9

17Instructions for installation and servicing ecoTEC 839592_12 Vessel Volume [L]Initial system pressure (bar) 1.0 1.5Pressure relief valve setting (ba

Page 10 - 3 General requirements

18 Instructions for installation and servicing ecoTEC 839592_124 Boiler installation sequence4.1 Transporting the appliance Caution!With regards to t

Page 11 - General requirements 3

19Instructions for installation and servicing ecoTEC 839592_12 Positioning of Appliance for Final Installation – above worktop, foreseeable obstructio

Page 12

2ContentsInstructions for installation and servicing ecoTEC 839592_121 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . 41.1 Note

Page 13

20 Instructions for installation and servicing ecoTEC 839592_124.2.2 Unpack the boilerTo unpack the boiler, cut both plastic carton straps, open box a

Page 14

21Instructions for installation and servicing ecoTEC 839592_124.5 Installing the flue system• Install the flue system (refer to the seperate air/flu

Page 15

22 Instructions for installation and servicing ecoTEC 839592_122673541Fig. 4.5 Fitting the gas connection (example ecoTEC plus com-bination boiler)•

Page 16

23Instructions for installation and servicing ecoTEC 839592_12 NoteFlush all foreign matter from the mains supply before connecting to the boiler.•

Page 17

24 Instructions for installation and servicing ecoTEC 839592_124.12 Heating connection Caution!When making final connection to the boiler, if using s

Page 18

25Instructions for installation and servicing ecoTEC 839592_12 Caution!To ensure fumes do not escape through the syphon of the boiler the trap must b

Page 19

26 Instructions for installation and servicing ecoTEC 839592_124.14.2 Connection to the main supplyFig. 4.13 Opening the electronics box• Remove the

Page 20 - Fig. 4.2 Assembly template

27Instructions for installation and servicing ecoTEC 839592_12 4.14.3 Electric board layoutBurner cable harnessHydraulic cable harnessConnection for

Page 21

28 Instructions for installation and servicing ecoTEC 839592_12X 2BUS— +24V7 8 9230VL N 3 4 5X 20X40X31X12X41Electronic c

Page 22

29Instructions for installation and servicing ecoTEC 839592_12 X 2BUS 24V7 8 9— +230VL N 3 4 5X 20X40X31X12X41Electronic

Page 23

3Instructions for installation and servicing ecoTEC 839592_12Contents6 Functional checks (commissioning part II). . 396.1 Functional checks . . . .

Page 24

30 Instructions for installation and servicing ecoTEC 839592_124.15 Controls4.15.1 Vaillant controls and accessoriesController Item no. ConnectionVR

Page 25

31Instructions for installation and servicing ecoTEC 839592_124.16 Thermostatic radiator valvesThe boiler has a built in automatic by-pass valve makin

Page 26 - -+789 LN 345

32 Instructions for installation and servicing ecoTEC 839592_125 Commissioning Part I5.1 Preliminary electrical checksCheck the electrical installatio

Page 27

33Instructions for installation and servicing ecoTEC 839592_12 The ecoTEC plus combination boiler will be delivered with a filling loop.• Insert the

Page 28 - Electronic control box

34 Instructions for installation and servicing ecoTEC 839592_125.6 Filling the condensate siphon1Fig. 5.4 Filling the condensate siphon Danger!Note t

Page 29

35Instructions for installation and servicing ecoTEC 839592_12 If the boiler version corresponds to the local gas family:• Proceed as described below

Page 30

36 Instructions for installation and servicing ecoTEC 839592_12BoilerNominal net heat input in kW as per BS EN 483Gas flow rateNatural gas in m3/h Pro

Page 31

37Instructions for installation and servicing ecoTEC 839592_12 • Connect a digital pressure gauge or U-tube manometer (2).• Open the gas isolation v

Page 32 - 5 Commissioning Part I

38 Instructions for installation and servicing ecoTEC 839592_125.10 Refitting the case12Fig. 5.9 Refitting the case• Hook the top of the front casing

Page 33 - Commissioning Part I 5

39Instructions for installation and servicing ecoTEC 839592_12 6 Functional checks (commissioning part II)6.1 Functional checks6.1.1 ProcedureAfter in

Page 34

4 Instructions for installation and servicing ecoTEC 839592_121 Introduction1 Introduction1.1 Notes on the documentationThe following information is

Page 35

40 Instructions for installation and servicing ecoTEC 839592_12• Release water from the system until the system design pressure of 1.0 bar is attaine

Page 36

41Instructions for installation and servicing ecoTEC 839592_12 7 Inspection and maintenance7.1 Inspection and maintenance intervals Danger!Risk of in

Page 37

42 Instructions for installation and servicing ecoTEC 839592_12- Correctness of electrical, water and gas connections.- Correctness of the water pre

Page 38

43Instructions for installation and servicing ecoTEC 839592_12 NoteThe boiler is fitted with a flue gas analysis point (4). A suitable flue gas analy

Page 39 - 6 Functional checks

44 Instructions for installation and servicing ecoTEC 839592_127.1.5 Inspection and maintenance work stepsNo. ActivityColumn 1 Inspection must be car

Page 40

45Instructions for installation and servicing ecoTEC 839592_127.2 Servicing the burner module7.2.1 Removing the burner moduleThe burner module consi

Page 41 - Inspection and maintenance 7

46 Instructions for installation and servicing ecoTEC 839592_127.2.2 Cleaning the integral condensation heat exchanger Caution!Protect the electronics

Page 42 - 7 Inspection and maintenance

47Instructions for installation and servicing ecoTEC 839592_12 Inspection and maintenance 710 9 8 4 5 7 6 Fig. 7.7 Refitting the burner module• Ins

Page 43

48 Instructions for installation and servicing ecoTEC 839592_12• Clean the siphon part section by rinsing it out with water.• Fill the lower part wi

Page 44

49Instructions for installation and servicing ecoTEC 839592_12 8 Troubleshooting8.1 Logical fault finding procedureThese checks must be carried out b

Page 45 - Inspection and maintenance 7

5Instructions for installation and servicing ecoTEC 839592_12 The ecoTEC system boiler consists of models with outputs of 12, 15, 18, 24, 30 and 37 kW

Page 46

50 Instructions for installation and servicing ecoTEC 839592_12In the diagnostic mode, you can change certain parameters or display more information.T

Page 47

51Instructions for installation and servicing ecoTEC 839592_12 Display Meaning Display value/adjustable valued.36 Hot water flow sensor in l/mind.40 F

Page 48

52 Instructions for installation and servicing ecoTEC 839592_12Display Meaning Display value/adjustable valued.50 Offset for minimum speed in rpm/10,

Page 49 - Troubleshooting 8

53Instructions for installation and servicing ecoTEC 839592_12 Code Meaning CauseF. 0 Flow–NTC open circuitNTC broken, NTC cable broken, Defective con

Page 50 - 8 Troubleshooting

54 Instructions for installation and servicing ecoTEC 839592_128.2 Test programsSpecial functions can be triggered on the appliances by activating var

Page 51

55Instructions for installation and servicing ecoTEC 839592_129.2 Replacing burner Danger!Before replacing the component, comply with the safety instr

Page 52

56 Instructions for installation and servicing ecoTEC 839592_129.4 Replacing expansion vessel Danger!Before replacing the component, comply with the s

Page 53

57Instructions for installation and servicing ecoTEC 839592_12 3 2 1 Fig. 9.6 Primary heat exchanger holder• Disconnect the plug-in connection (2) of

Page 54 - 9 Parts replacement

58 Instructions for installation and servicing ecoTEC 839592_1210 Recycling and disposalBoth the Vaillant ecoTEC and the associated transport packagi

Page 55 - Parts replacement 9

AppendixEG declaration of conformityAppendix

Page 56

6 Instructions for installation and servicing ecoTEC 839592_122 Boiler specifications2.1 Technical dataTechnical dataecoTEC plus ecoTEC proUnits824 83

Page 57

Installation,Commissioning andService RecordInstallation,Commissioning andService Record

Page 58 - 11 Vaillant service

Please affix the label from therear cover of the control boxover this area.

Page 59 - Appendix

SERVICE INTERVAL RECORDIt is recommended that your heating system is serviced regularly and that you complete the appropriate Service Interval Record

Page 61

839592_12 GBIE 062010 — Subject to alterations

Page 62 - SERVICE INTERVAL RECORD

7Instructions for installation and servicing ecoTEC 839592_12 Technical dataecoTEC plusUnits612 615 618 624 630 637CH heat output range 80 °C flow/60

Page 63

8 Instructions for installation and servicing ecoTEC 839592_122.2 Dimensions2412064272088312510010044035 35130180300ecoTEC plus 630:334ecoTEC plus 637

Page 64

9Instructions for installation and servicing ecoTEC 839592_122.3 Installation1 2 3 4 6 5 7 8 9 14 13 111012Fig. 2.2 Function elements of combination b