Sheet F Check operation of differential pressure switch
Does sparking start
at burner?
Does red lockout indicator
( ) glow after 10 seconds?
Replace
main switchboard
Is gas solenoid
activated?
Is differential pressure
switch activated?
Has system been filled
with water?
Fill and vent
system and boiler
Check for dirt or damage to the differential
pressure switch, supply tubes and diaphragm
Go to sheet H
Go to sheet G
Check continuity of
microswitch. Replace
if necessary. Check
connection of plug X11
to main switchboard.
If burner still fails
to light, replace main
switchboard
Yes
No
No
Yes
No
No
Yes
Yes
No
Yes