8.3 General Installation Diagram
Warning!
Danger of breakdowns or malfunction.
Observe the minimum assembly distances
indicated in Figure 8.1.
Fig. 8.1 General diagram of the installation and the minimum
assembly distances.
Legend
1 Indoor Unit
2 Outdoor Unit
3 Pipe for draining the condensed water
A Front separation (minimum 10 cm)
B Top separation in relation to the ceiling (minimum 5 cm)
C Separation fixing wall (minimum 10 cm)
D Height in relation to the floor (minimum 2 m)
E Side separation opposite side connections (minimum 10 cm)
F Rear separation (minimum 10 cm)
G Side separation connections side (minimum 15 cm)
H Front separation (minimum 60 cm)
9 Installation of the Indoor Unit
9.1 Selecting the Assembly Location
Warning!
Danger of breakdowns or malfunction.
Observe the minimum assembly distances
indicated in Figure 8.1.
Note!
If a hole already exists in the wall or a coolant
pipe or condensed water pipe has already been
installed, the base plate can be mounted to adapt
to these conditions.
Recommendations
- Install the indoor unit close to the ceiling.
- Choose a mounting site that will allow air to reach all
parts of the room evenly. Avoid beams, installations or
lights which obstruct the airflow.
- Install the indoor unit at an adequate distance from
chairs or workstations in order to avoid unpleasant
draughts.
- Avoid close heat sources.
9.2 Fixing the Assembly Plate
Carry out the steps described below:
• Place the mounting plate on the chosen installation
point.
• Level the plate horizontally and mark the holes to be
made on the wall for the installation using the screws
and rawplugs.
• Remove the plate.
Warning!
Danger of breaks in the domestic installation.
Check that there are no electricity lines, pipes or
any other element which could be impaired
behind the spots where the holes are to be
drilled.
If so, choose another installation location and
repeat the aforementioned steps..
• Make the holes using a drill and insert the rawplugs.
• Place the assembly plate in the assembly location,
level it horizontally and fix it with the screws and the
rawplugs.
Warning!
Danger of breakdowns or malfunction.
Ensure that the assembly plate has been
correctly levelled.
Otherwise, disassemble the plate and assemble it
again correctly.