7 Gas supply adjustments (Commissioning Part II)
Instructions for installation and servicing aquaPLUS VUI 362-726
Fig. 7.3: Setting the maximum heating load (nominal load)
1
10
2
I
0
7.3 Adjusting to the maximum heat load (nominal
load)
Remove the cap (1).
Set the DHW temperature control to maximum and
fire the boiler at full rate by fully opening a hot water
tap.
Turn off the boiler at the main ON/OFF control.
Press and hold the "+" button, while pressing the
button turn the main ON/OFF control to the "1" ON
position.
Continue holding "+" button until display alternates
between "P1, P2, P3, P11, P12 and P13". Release "+"
button.
Press "+" button until "P1" (full gas rate) is shown in
display.
Press "i" button to operate boiler at full gas rate.
Using a 10 mm spanner turn nut (2) to adjust the
burner operating pressure.
- Turn the nut (2) clockwise to increase the nominal
load
- Turn the nut (2) anticlockwise to decrease the
nominal load.
Adjust the burner pressure until it matches the
maximum output as detailed in table 7.7, page 30.
Now turn the 10 mm nut (2) anticlockwise until the
burner pressure drops by approx. 0.3 - 0.4 mbar.
Nominal load is now correctly adjusted.
Refit the plastic cap (1).
Warning!
The plastic cap (2)must be fitted for the gas
valve assembly to function correctly.
Turn off the hot water tap.
To cancel selected "P1" or "P2" mode press the "i"
and "+" buttons simultaneously.