Boiler Installation Sequence 5
Instructions for Installation and Servicing turboMAX pro R3 15
5.8 Cold water mains inlet and hot water outlet
Flush all foreign matter from the mains supply before
connecting to the boiler.
Connect the cold water service valve (1) to the cold
inlet water connection (3) of the appliance with the
washer (2) provided and tighten.
Connect the cold water inlet pipe copper tail to the
cold water service valve and tighten.
Connect the 15 mm hot water outlet copper tail (4) to
the hot water outlet connection of the appliance (6)
with the washer provided (5) and tighten.
Note!
The hot water outlet union nut is packed in with
the PRV fitting pack.
Fig. 5.7: Fitting the hot and cold water connections
1
2
3
4
6
I
0
5.9 Central heating flow and return pipework
Before connecting the heating circuit to the boiler appli-
ance, all pipework and radiators must be thoroughly
flushed to remove any installation debris.
Connect the central heating flow (4) and return (1) ser-
vice valves to the appliance (6 and 3) with the washers
provided (2 and 5) and tighten the nuts. Ensure that
the valve spindles face downwards and the drain
points face to either side of the boiler.
Connect the central heating pipework to the flow (4)
and return (1) tails.
Pressure Relief Valve
Connect a discharge pipe not less than 15 mm diameter
to the outlet of this valve.
The discharge pipework should be as short as possible
and installed with a continuous fall away from the boiler.
The pipe should terminate in a position which ensures
that any discharge of water or steam from the valve
cannot create a hazard to persons in or about the premi-
ses, or cause damage to any electrical components or
external wiring, and the point of discharge should be
clearly visible (see diagram in plastic bag).
Fig. 5.8: Central heating flow and return pipework