Vaillant TURBOmax VUW 242 E Service Manual Page 34

  • Download
  • Add to my manuals
  • Print
  • Page
    / 44
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 33
10 Fault Finding
Instructions for Installation and Servicing turboMAX pro R334
Check gas valve and central heating system pressure
Does burner light 1st
attempt?
Does burner light within 3
ignition attempts?
No
Yes
Check gas supply
Does burner light?
Yes
Check burner pressure
settings are correct
Yes
No Reset boiler
No
Check/replace gas valve
as necessary and
Does burner light?
No
Replace electronic board
Yes
Is burner indicator
illuminated?
No
Check flame
rectification lead and
electrode
Is burner indicator
illuminated
No
Yes
Does burner shut down after
approx. 15 secs.
No Go to sheet F
Yes
Check water pressure in
central heating system, refill
and vent. as necessary
Check pump is running?
Yes
Yes Replace pump
No
Is 230 VAC present at the
pump plug connection?
No
Replace electronic board
Sheet E
Does yellow ignition indicator flash?
check water pressure
833792_41GB_012005.qxd 09.03.2005 16:47 Uhr Seite 34