24 Installation Manual auroMATIC 560
10 Technical data
Features Units auroMATIC 560
Operating voltage
Controller current consumption
Contact load of output relays (max.)
Maximum total current
V AC/Hz
W
A
A
230/50
max. 10
2
4
Shortest switching interval
Power reserve
Maximum ambient temperature
Sensor operating voltage
min
min
°C
V
10
30
50
5
Minimum cross-sections
Sensor wires mm
2
0.75
230 V power wires mm
2
1.5
Controller housing dimensions
Height mm 175
Width mm 272
Depth mm 55
Level of protection
Protection class for controller
IP 20
II
Table 10.1 Technical data
11 Sensor characteristics
VR 10 standard sensor, type NTC 2.7 K
Sensor values Resistance value
0 °C 9191 Ohm
5 °C 7064 Ohm
10 °C 5214 Ohm
20 °C 3384 Ohm
25 °C 2692 Ohm
30 °C 2158 Ohm
40 °C 1416 Ohm
50 °C 954 Ohm
60 °C 658 Ohm
70 °C 463 Ohm
80 °C 333 Ohm
120 °C 105 Ohm
Table 11.1 VR 10 standard sensor characteristics
VR 11 standard sensor, type NTC 10 K
Sensor values Resistance value
-20 °C 97070 Ohm
-10 °C 55330 Ohm
-5 °C 42320 Ohm
0 °C 32650 Ohm
5 °C 25390 Ohm
10 °C 19900 Ohm
15 °C 15710 Ohm
20 °C 12490 Ohm
25 °C 10000 Ohm
30 °C 8057 Ohm
35 °C 6532 Ohm
40 °C 5327 Ohm
50 °C 3603 Ohm
60 °C 2488 Ohm
70 °C 1752 Ohm
80 °C 1258 Ohm
90 °C 918 Ohm
100 °C 680 Ohm
110 °C 511 Ohm
120 °C 389 Ohm
130 °C 301 Ohm
Table 11.2 VR 11 standard sensor characteristics