5Operating Manual auroMATIC 560
a temperature of at least 68 °C has been maintained for
a period of 30 minutes.
The heating engineer activates the anti-Legionnaires
disease protection in the installer level and specifies
whether the heating process should take place at 3:30
p.m. or at 4:00 a.m. (if the electricity is cheaper then).
4.6 Anti-seize protection for pumps
If no pumping has occurred for 23 hours, all installed
pumps are switched on for approx. 3 seconds to prevent
pumps from seizing.
4.7 Circulation
If you only have one collector array connected, a circula-
tion pump can be connected to the controller. You can
specify up to three heating windows for the circulation
pump in the timer program (see Sec. 5.4.4). Set up the
time program so that the circulation pump only operates
at times when you expect a supply of hot water will be
needed. Otherwise the circulation pump operates unnec-
essarily and inadvertently cools down the cylinder.
4.8 Calendar
The controller is equipped with a calendar so that it can
automatically adjust for daylight-savings time. To acti-
vate it, simply enter the current date in the installer
level.
Note!
In the event of a power failure, the controller
only has a power reserve of 30 minutes. After
30 minutes, the internal clock stops and the
calender will not automatically resume function
once power has been restored. In this case the
time and date will need to be reset.
4.9 Controlling activation duration
Activation duration controlling serves to keep the solar
circuit at the activation value, and thus in operation, for
as long as possible. The pump is switched on and off in
periodical bursts depending on the difference between
the collector temperature and lower cylinder sensor.
When the activation difference is reached, the function
is started (if activated) with an activation duration of
50 % - i.e., the pump is switched on for 30 seconds and
then switched off for 30 seconds. If the difference in
temperature increases, the activation duration is pro-
longed (e.g., 45 sec. on, 15 sec. off). When the difference
in temperature decreases, the activation duration is
reduced (e.g., 20 sec. on, 40 sec. off). The period length
is always a minute.
Activation duration control is activated in the installer
level.
4.10 Special functions
Please refer to Sec. 5.6 for information on how to acti-
vate the following special functions.
4.10.1 Party function
When the party function is activated, the reheating func-
tion is enabled. This means that the set target value for
the cylinder will be maintained by reheating if necessary.
4.10.2 One-time reheating
When this function is activated, the cylinder tempera-
ture is reheated to the set level one time.
4.10.3 Holiday function
When this function is activated, the operating
mode is switched to “Off” for the set holiday period (1 to
99 days). This deactivates both the solar heating and
the reheating function.
5 Operation
5.1 Operating the controller
The controller has a display which consists of symbols,
and was designed according to the Vaillant “turn and
click” concept. You can call up and set values by turning
the dial. You can also click the dial in order to call up val-
ues within an operating level. You can access the operat-
ing and display levels with the three selection buttons.
To prevent operating errors, the programming button
must be held down for approx. three seconds to reach
the installer level.
5.2 Overview of the control elements
1
2
Fig. 5.1 Controls
Key
1 Display
2 Dial (turn and click)
i Info button
F Special functions button
P Programming button
Functions 4