4 Operating Manual auroMATIC 560
3.2 Intended use
The auroMATIC 560 solar controller is a state-of-the-art
appliance which has been constructed in accordance
with recognised safety regulations. Nevertheless,
improper use can cause serious or fatal injury to the
user or others, and the appliance or other property can
be damaged.
The appliance is a control system for regulating warm
water storage with solar heating, and supports reheating
with a boiler or with an electric heating rod.
Any other use or extended use is considered to be
improper. The manufacturer or supplier is not liable for
any resulting damage. The user alone bears any risk.
Intended use includes the observance of the operating
manual and all related documents.
Caution!
Any improper use is forbidden.
3.3 Requirements for the installation site
The controller must be installed in a dry room.
3.4 Care
You can clean the housing of the controller with a damp
cloth and a little soap.
Note!
Do not use scouring or cleaning agents which
could damage the display.
3.5 Recycling and disposal
Neither the controller or any of its accessories belong in
the household waste. Make sure the old appliance and
any existing accessories are disposed of properly.
4 Functions
4.1 Solar yield
The solar controller works on the principle of differential
temperature control. The controller always switches on
the collector pump when the difference in temperature
(collector temperature - cylinder temperature) is greater
than the programmed activation difference.
The controller switches off the collector pump when the
difference in temperature (collector temperature - cylin-
der temperature) is less than the programmed activation
difference.
The heating engineer sets the parameters to the install-
er level when the solar controller is installed.
The solar yield is determined from:
The difference in temperature between the collector‘s
forward flow and return flow
The set flow value at the control valve of the flow rate
limiter (set during installation)
The operating time of the collector pump
During installation the heating engineer sets the flow
rate limiter and enters the flow rate into the solar con-
troller at the installer level. The solar yield is calculated
by the solar controller. The total yield can be called up
and reset in the installer level.
4.2 Reheating
The reheating function allows the cylinder to heat up to
the required temperature during a set time window, even
if the solar energy yield is insufficient. In this case the
water can be reheated using an external heater or an
electrical heating rod. You can set up time windows for
reheating the solar cylinder (see Sec. 5.5.3 for details).
4.3 Reheating delay
To prevent unnecessary reheating by an external heater
or an electrical heating rod, the controller is equipped
with a reheating delay function. This function delays
reheating by up to 30 min. in case the collector pump is
running and the solar yield becomes available. If the col-
lector pump remains off and/or the desired cylinder tem-
perature is not reached after the delay period, the cylin-
der will be reheated using the external heater or electi-
cal heating rod.
The reheating delay function is activated in the expert
level.
4.4 Connecting a second storage cylinder
You can connect up to two solar cylinders to the control-
ler. The cylinder with the higher maximum temperature
will be considered as the priority cylinder. The priority
cylinder will always be heated if the collector tempera-
ture is greater than than actual temperature plus the set
activation difference. The heating of the the cylinder will
stop once the maximum temperature for the cylinder is
reached, or if the collector temperature is less than the
actual cylinder temperature plus the set activation dif-
ference.
The second cylinder can only be heated when the first
cylinder is not being heated. The same activation and
deactivation conditions apply here as well.
4.5 Anti-Legionnaire’s disease protection
The anti-Legionnaire‘s disease protection function is
designed to kill germs in the cylinder and pipes.
When the function is activated, the cylinder, the corre-
sponding hot water pipes, and the circulation pump (if
installed), are brought to a temperature of 70 °C once a
week (Wednesday, 14:00).
In doing so, the cylinder temperature is raised to 70 °C
and the corresponding circulation pump is switched on
(if installed). First, an attempt will be made using solar
yield alone to reach the target temperature over a
90 min. period. If this is not successful, the anti-
Legionnaire’s disease protection is carried out using an
external heater or an electric heating rod, if one or the
other has been installed for reheating. The anti-
Legionnaire’s disease protection function will stop once
3 Information on installation and operation
4 Functions
Page view 3