Vaillant ecoTEC plus 937 Service Manual Page 17

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 16
Installation and maintenance instructions ecoTEC plus 937 0020031552_06 17
Location of the junction mm
A Directly under or above an opening or the horizontal
to an opening, a hollow ventilation tile, an opening
window etc.
300
B Under gutters, soil pipes or drainpipes 75
C Unter eaves 200
D Under balconies 200
E From vertical drainpipes and down-pipes 25
F From external and internal corners 300
G Above the ground, a roof or a balcony 300
H Opposite another surface 600
I Opposite another termination 1200
J Next to an opening (e.g. a door, window) within a
car-port
1200
K Vertically away from a junction on the same wall 1500
L Horizontally away from a junction on the same wall 300
M Distance away from an adjoining vertical flue pipe 500
Table 4.2 Position of the terminal in a fan-assisted concentric
flue
i
In addition, the terminal should not be located
closer than 150 mm from an opening in the fab-
ric of the building formed for the purpose of
accommodating a built-in element such as a
window.
BS 5440–1: We recommend that the terminal of a
fan-assisted flue system be positioned as follows:
a) At least 2 m from an opening in the building
directly opposite, and
b) so that products of combustion are not directed
to discharge across a boundary.
1) Dimensions B, C and D:
These dimensions can be reduced to 25 mm
without having a negative effect on the per-
formance of the boiler. In order to ensure that
condensate plume does not affect adjacent sur-
faces the terminal should be extended as shown
in Fig. 3.7.
2) Dimension F:
These dimensions can be reduced to 25 mm
without having a negative effect on the output
of the combi boiler. However in order to ensure
that the condensate plume doe not affect adja-
cent surfaces a clearance of 300mm is pre-
ferred. For IE, recommendations are given in
the current edition of IS813.
Fig. 4.7 Flue termination under balcony/eaves
4.6 Air supply
Detailed recommendations for air supply are given in
BS 5440, Part 2.
It is not necessary to have an air vent in the room or
internal space in which the boiler is installed.
Ventilating a cabinet or enclosure
This appliance is highly efficient. As a consequence the
heat loss from the casing is very small. For cupboard or
compartment installations it is not necessary to provide
any high or low permanent air vents for cooling or ven-
tilation purposes.
4.7 Electrical connection
e
Danger!
Risk of death from electric shock.
If the appliance is not earthed, it may hold
voltage if a defect occurs.
Earth the appliance.
In accordance with BS 7671 (IEE Wiring Regulations) and
any other local regulations which may apply, a 3 A
fused single phase AC supply (230 V, 50 Hz) must be
provided. In IE the current issue of the ETCI regulations
must be observed. The method of connection to the
mains electricity supply must provide a means of
completely isolating the boiler and ancillary controls.
Isolation is preferably by the use of a fused three pin
plug and unswitched shuttered socket outlet, both com-
plying with the requirements of BS 1363. Alternatively, a
3 A fused double pole switch with 3 mm contact separa-
tion on both poles may be used.
>
General requirements 4
Page view 16
1 2 ... 12 13 14 15 16 17 18 19 20 21 22 ... 79 80

Comments to this Manuals

No comments