Installation and maintenance instructions ecoTEC plus 937 0020031552_06 69
b
Caution!
Possible material damage caused by loos-
ening or retightening the screws.
The primary heat exchanger may become
damaged.
You must not loosen or tighten the four
screws (fig. 8.4, 1).
b
Caution!
Possible material damage caused by lubri-
cating the seals.
Mineral oil-based lubricants may damage the
seals. The seals should therefore not be lubri-
cated.
Only use water or commercially available
soft soap, if necessary, to assist with
installation.
Insert the flow and return connection into
the primary heat exchanger as far as pos-
sible and make sure the brackets on the
flow and return connection are seated
properly.
Filling and vent the combi boiler as required.
After completion of the work check the system for
gas leaks and carry out a function test (see Section
8.8).
10.6 Replacing the expansion vessel of the shift
load storage tank
a
Danger!
Risk of personal injury and/or material
damage as a result of non-compliance with
the safety instructions.
Before replacing the component, comply
with the safety instructions in Chapter 10.1.
Disconnect the appliance from the mains as described
in Section 10.1, and close the gas isolator valve in the
gas supply pipe.
Close the cold water inlet stop valve.
Open a hot water tap in order to release the pressure
on the water circuit. Then close the tap again.
Remove the screw on the cover of the shift load stor-
age tank.
Remove the cover.
>
>
>
>
>
>
>
>
>
>
>
1
2
Fig. 10.7
Replacing the expansion vessel of the shift load stor-
age tank
The expansion vessel (1) is freely accessible.
Release the nuts (2) on the expansion tank.
Pull the expansion tank (1) off the pipe fitting and
remove it from the EPS trough.
Insert the new expansion tank in the EPS trough.
Re-connect the new expansion tank. Use a new gas-
ket:
Check the pressure of the expansion tank (minimum
pressure 4 bar).
Filling and vent the combi boiler and the shift load
storage tank.
After completion of the work check the system for
gas leaks and carry out a function test (see Section
8.8).
10.7 Replacing the storage tank pump of the shift
load storage tank
a
Danger!
Risk of personal injury and/or material
damage as a result of non-compliance with
the safety instructions.
Before replacing the component, comply
with the safety instructions in Chapter 10.1.
Isolate the unit from the mains as described in Sec-
tion 10.1.
Close the gas isolator valve in the gas supply pipe.
Close the stop valves in the hot water system and
drain the water out of the combi boiler and the shift
load storage tank.
>
>
>
>
>
>
>
>
>
>
>
>
Replacing components 10