50 Instructions for installation and servicing ecoTEC 839592_12
In the diagnostic mode, you can change certain
parameters or display more information.
The diagnostic information is divided into two diagnostic
levels. The second diagnostic level can be reached only
after entering a password.
Caution!
Access to the second diagnostic level must be
used exclusively by a qualified technician.
First Diagnostic level
• Press the i” and “+” keys simultaneously.
The display shows “d.0”.
• Use the +” or “” keys to scroll through the desired
diagnostic numbers of the first diagnostic level (see
Table 8.2).
• Press the i” key.
Display Meaning Display value/adjustable value
d. 0 Heating part load Adjustable heating part load in kW (factory setting: max. output)
d. 1 Water pump over run time for heating mode 2 - 60 min (factory setting: 5 min)
d. 2
Max. burner anti cycling period at 20 °C Flow
temperature
2 - 60 min (factory setting: 20 min)
d. 3
Hot water flow temperature reading (combination boiler
only)
in °C
d. 4
Current temperature for warm start sensor
(combination boilers only)
Current storage tank sensor (system boilers only)
in °C
d. 5
Flow temperature target value or return target value
when return regulation is set.
in °C, max. the value set in d.71
Limited by the eBUS controller (if an eBUS controller is connected)
d. 6 Hot water temperature target value in °C, 35 to 65 °C
d. 7
Warm start temperature target value
(ecoTEC plus combination boiler only)
Storage temperature target value (system boiler only)
in °C, 40 to 65 °C
in °C, 15 °C for left stop, then 40 to 70 °C
d. 8 External controls heat demand (Clamp 3-4)
0 = open (no heat request)
1 = closed (heat request)
d. 9
Flow target temperature from external analogue
regulator to terminal 7-8-9/eBUS
in °C, minimum from ext. eBUS target value and target value terminal
7
d.10 Status internal heating pump 1 = on, 0 = off
d.11 Status external heating pump 1 to 100 = on, 0 = off
d.12 Cylinder charging pump (via accessory module) 1 to 100 = on, 0 = off
d.13 Hot water circulation pump (via accessory module) 1 to 100 = on, 0 = off
d.22 Hot water demand 1 = on, 0 = off
d.23 Summer/Winter function 1 = Winter, 0 = Summer
d.25 Hot water activation via eBUS Control 1 = yes, 0 = no
d.30 Control signal for both gas valves 1 = on, 0 = off
d.33 Fan speed target value in rpm/10
d.34 Fan speed actual value in rpm/10
d.35 Position of diverter valve (combination boilers only) 0 = Heating; 100 = Hot water; 40 = Centre position
Table 8.2 Diagnostic codes of the first diagnostic level
The display shows the relevant diagnostic information.
If necessary, use the “+” or “” keys to change the
value (display flashes).
Save the new value by holding down the “i” key for
approx. 5 seconds until the display no longer flashes.
You can end the diagnostic mode as follows:
• Press the i” and “+” keys simultaneously.
or
Do not press any key for approx. 4 minutes.
The current heating flow temperature appears in the
display again.